47
Lutron® integration protocol
Quantum® (continued)
Integration Access Points (continued)
Connection Information
Provides an RS232 and Ethernet connection to communicate with external equipment.
RS232
The RS232 connection has the following communication settings:
• Baud Rate 9600/19200/38400/115200 (set via dipswitch on unit)
• 8 data bits
• No parity bit
• 1 stop bit
• No flow control
Ethernet
Configuring the control interface to communicate over a network takes not only knowledge of
the Quantum® system, but of networking as well. Installers with limited networking knowledge
are advised to contact a networking professional before attempting to connect a QSE-CI-NWK-E
through a network. The information below will help an installer communicate the QSE-CI-NWK-E
configurations to a network professional.
The installer will make any necessary changes to the control interface using the Lutron® DeviceIP or
Quantum® PC software tool and the network professional can make any necessary changes to the
networking equipment.
Single Ethernet Port
• IEEE® 802.3 Auto-Sensing 10BaseT / 100BaseTX
• Supports MDI/MDIX auto-crossover (no crossover cable needed).
• Female 8P8C “Computer RJ-45” socket
• Green “Connect” LED, Amber “Activity” LED
• Use Cat 5 cabling or better
TCP / IP Settings
• IP Address: <static default = 192.168.250.1>
• Subnet Mask: <static default = 255.255.255.0>
• Gateway: <static default = 0.0.0.0>
Protocols Used for Integration
• TELNET
Telnet Server
• Used by third party equipment (e.g., touch screen)
• Limited to transferring ASCII characters
• Telnet Port number is 23
• Login #1: nwk
• Login #2: nwk2