Lutron® integration protocol
Sivoia® QS Venetian Blind (continued)
OUTPUT Commands (continued)
Example OUTPUT Messages
Examples presume shade has been assigned Integration ID 1.
Operation Command String
Execute: #OUTPUT, Integration ID, Action Number, Parameters
Set Venetian blind to lift 0%, tilt 50% #OUTPUT,1,10,0,50<CR><LF>
Start raising Venetian tilt. #OUTPUT,1,11<CR><LF>
Stop raising Venetian tilt. #OUTPUT,1,13<CR><LF>
Query: ?OUTPUT, Integration ID, Action Number
What is the state of the Venetian lift and tilt? ?OUTPUT,1,10<CR><LF>
Response
1
: ~OUTPUT, Integration ID, Action Number, Parameters
Venetian lift level is 0%, tilt level 50%. ~OUTPUT,1,10,0.00,50.00<CR><LF>
NOTE
1. The system will report the target lift level and target tilt level of a Venetian blind. The actual levels are not transmitted
while it is moving. Example: If the Kitchen Venetian (Integration ID 1) is set at 25% lift and 75% tilt, and is
commanded to go to 100% lift and 50% tilt by sending #OUTPUT,1,10,100,50, the response from the system will be
~OUTPUT,1,10,100.00,50.00