Lutron® integration protocol
MONITORING Command-specific fields
Monitoring Type:
Description Monitoring Type
Diagnostic Monitoring 1
Event Monitoring 2
Button Monitoring 3
LED Monitoring
1
4
Zone Monitoring 5
Occupancy 6
Scene # 8
System Variable 10
Reply State (if disabled, all messages FROM the integration access point will cease) 11
Prompt State (if disabled, the prompt will not be printed to the terminal) 12
Venetian Tilt
2
14
Sequence Monitoring
1
16
HVAC Monitoring
1,2
17
Mode Monitoring
1,2
18
Shade Group Monitoring
3
23
Partition Wall
3
24
Set (#) or Get (?) State of All Monitoring (except Reply and Prompt) 255
NOTES
1. Not supported in QS Standalone.
2. Not compatible with Quantum®.
3. Not supported in RadioRA® 2.
Action Numbers:
Action Action Number
Enable 1
Disable 2
MONITORING Command Formats
Use “MONITORING Command-specific fields” tables
to complete these command fields.
Operation
Command
#MONITORING, Monitoring Type, Action Number
Integrator’s Reference (continued)
MONITORING: Command Summary
Monitoring allows the user to configure what types of messages the system will report.
Note to Integrator: The default values of these are set in the programming database and restored