122
Lutron® integration protocol
Maestro® Dimmer (continued)
OUTPUT Commands
OUTPUT Command Format
OUTPUT Command-specific fields
Action Numbers and Parameters:
Action Action Number Parameters
Set or Get Zone Level 1 Level = 0 –100 or 0.00 –100.00
Fade
1
in: SS.ss
2
, SS, MM:SS, or HH:MM:SS
Delay
1
in: SS.ss
2
, SS, MM:SS, or HH:MM:SS
Start Raising 2 None
Start Lowering 3 None
Stop Raising / Lowering
4 None
Start Flashing
3, 4, 5
5 Fade
1
in: SS.ss
2
, SS, MM:SS, or HH:MM:SS
Delay
1
in: SS.ss
2
, SS, MM:SS, or HH:MM:SS
NOTES
1. The Fade and Delay time are optional. When not used, the system will use a one-second fade time with zero-second delay.
2. Fractional seconds “SS.ss” will be rounded down to the nearest quarter second. For example, if a fade time is specified
as 1.31 seconds a value of 1.25 seconds will be used.
3. The system will not report a level while the output is flashing, it will instead report that it is flashing.
4. Default flash every second, unless fade time is specified (flash period is 2× fade time).
5. To stop a dimmer from flashing, send it to a valid level.
Example OUTPUT Commands
Examples presume dimmer has been assigned Integration ID 1.
Operation Command String
Execute: #OUTPUT, Integration ID, Action Number, Parameters
Set dimmer to 75% with a 1 min 30 sec fade. #OUTPUT,1,1,75,01:30<CR><LF>
Start Raising dimmer level. #OUTPUT,1,2<CR><LF>
Stop Raising / Lowering dimmer level. #OUTPUT,1,4<CR><LF>
Query: ?OUTPUT, Integration ID, Action Number
What is the state of the output? ?OUTPUT,1,1<CR><LF>
Response
1
: ~OUTPUT, Integration ID, Action Number, Parameters
Output level is set to 90%. ~OUTPUT,1,1,90.00<CR><LF>
NOTE
1. The system will report the target level of a dimmer while it is fading from one level to another.
The actual level is not transmitted while dimming between levels.
Example: If the “Over Sink” (1) dimmer is at 20% and is then commanded to go to 100% by sending
#OUTPUT,1,1,100,
the response from the system will be ~OUTPUT,1,1,100.00
Use “OUTPUT Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)
#OUTPUT, 1, Action Number, Parameters