134
Lutron® integration protocol
HVAC Command-specific fields (continued)
Action Numbers and Parameters (continued):
Action Action Number Parameters
Get (?) Call Status 14
0 = None, Last was Heat
1 = Heat Stage 1
2 = Heat Stage 1 and 2
3 = Heat Stage 1, 2 and 3
4 = Heat Stage 3
5 = None, Last was Cool
6 = Cool Stage 1
7 = Cool Stage 1 and 2
8 = Off
9 = Emergency Heat
10 = Dry
Get (?) Current Temperature (°C)
1
15 Temperature = 0 – 100 °C
Set (#) or Get (?) Heat and Cool
Setpoints (°C)
1
with Eco effect applied
16
Heat Setpoint = 0 – 100 °C
Cool Setpoint = 0 – 100 °C
Set (#) or Get (?) Heat and Cool
Setpoints (°C)
1
17
Heat Setpoint = 0 – 100 °C
Cool Setpoint = 0 – 100 °C
NOTE
1. HomeWorks® QS software version 4.1 and higher.
Example HVAC Commands
Operation Command String
Execute: #HVAC, Integration ID, Action Number, Parameters
Set Heat Setpoint to 68 °F and Cool Setpoint to 72 °F. #HVAC,1,2,68,72<CR><LF>
Set System Mode to Cool. #HVAC,1,3,3<CR><LF>
Turn Eco Mode On. #HVAC,1,5,2<CR><LF>
Query: ?HVAC, Integration ID, Action Number
What is the Current Temperature? ?HVAC,1,1<CR><LF>
What is are the settings for Schedule 1, Event 2? ?HVAC,1,9,1,2<CR><LF>
What days are running Schedule 1? ?HVAC,1,10,1<CR><LF>
Response: ~HVAC, Integration ID, Action Number, Parameters
Current Temperature is 70 °F. ~HVAC,1,1,70<CR><LF>
Schedule 1, Event 2 starts at 8:00am with SPH=65,SPC=78 ~HVAC,1,9,1,2,08,00,65,78<CR><LF>
Schedule 1 is being run on Monday and Tuesday. ~HVAC,1,10,1,06<CR><LF>
HVAC Controller (continued)
HVAC Commands (continued)