Installation of GRAFIK5000 / GRAFIK6000 / GRAFIK7000 System 5
• Use wallboxes with a minimum depth of
2-3/4 in. (70 mm) for Control Station Devices
(CSDs)
• Multigang installations may require spacers
between wallboxes
• Mount wallboxes between flush and 1/8 in. (3
mm) below finished wall surface
• Finished wall should not have gaps around the
wallbox of greater than 1/8 in. (3 mm)
• Ground metal Wallboxes whenever possible
Drywall
Wallbox
2-3/4 in.
(70 mm)
min.
1/8 in.
(3 mm)
max.
Mount Wallboxes
Mounting of a single-gang US wallbox shown.
See the instructions sent with each individual
CSD for mounting requirements and
instructions.
Mounting frame orientation of a single-gang
EGRX product shown.
Mounting
Frame
Wall
Wallbox