SIMATIC S7-1200
Analog modules
SB 1232 analog output module
4/76
Siemens ST 70 · 2011
■
Overview
• Analog output for the SIMATIC S7-1200
• Can be plugged direct into the CPU
■
Technical specifications
6ES7 232-4HA30-0XB0
Product type designation SB 1232 1x AO
Supply voltages
Power supply to the transmitters
• Supply current, max. 25 mA
Current consumption
from backplane bus 5 V DC, typ. 15 mA
Power losses
Power loss, typ. 1.5 W
Analog outputs
Number of analog outputs 1
Cycle time (all channels) max.
Voltage: 300 S (R), 750 S (1 uF)
Current: 600 ms (1 mH); 2 ms
(10 mH)
Output ranges, voltage
• -10 to +10 V Yes
Output ranges, current
• 0 to 20 mA Yes
Load impedance (in rated range of
output)
• with voltage outputs, min. 1000
• with current outputs, max. 600
Cable length
• Cable length, shielded, max. Shielded, twisted wire pair
Analog value creation
Measurement principle Differential
Integrations and conversion time/
resolution per channel
• Resolution (incl. overrange) U / 12 bit, I / 11 bit
Smoothing of measured values
• parameterizable Yes
Errors/accuracies
Temperature error
(relative to output area)
25°C ±0.5% bis 55°C ±1%
Alarms/diagnostics/status infor-
mation
Alarms
•Alarms Yes
Diagnostics
• Diagnostic functions Yes
Diagnostic indication LED
• For status of the outputs Yes
Climatic and mechanical condi-
tions for storage and transport
Climatic conditions for storage and
transport
• Free fall
- Drop height, max. (in packaging) 0.3 m; five times, in dispatch
package
•Temperature
- Permissible temperature range -40 °C to +70 °C
• Air pressure acc. to
IEC 60068-2-13
- Permissible air pressure 1080 to 660 hPa
• Relative humidity
- Permissible range (without
condensation) at 25 °C
95%
© Siemens AG 2011
© Siemens AG 2011