ARCHITECTURAL WALL BOX DIMMERS
MONET
®
ARCHITECTURAL WALL BOX DIMMERS
MONET
®
GANGING & DERATING
Multi-gang wallplates are available for every permissible combi-
nation of small fin and large fin dimmers. The Wallbox Require
-
ments tables on the following pages can be used to determine
how many boxes are required for the application.
• When small and large fin devices are combined, all the large fin
devices must be placed to one side and all the small fin devices
must be placed to the other side.
• In an installation where all the fins are broken off, do not
remove the fins from the dimmers at each of the extreme ends
of the installation.
Multi-Gang Installation
• Install dimmers whenever possible without breaking off fins so
that derating is not necessary—even when ganging. If an in-
stallation requires fins to be broken off for space requirements,
derating is required.
• When ganging combinations of narrow and wide dimmers or
when ordering a custom wallplate, keep in mind that narrow
dimmers must be grouped together at one end of the gang
and all wide dimmers at the other end of the gang.
• Use adapter plates (Cat. No. MN0LA or MN0S
A) to enable use
of ANY Decora
®
device in a Monet multi-gang installation.
CAUTION: Do not gang dimmers vertically, one directly above another.
No Fins Broken Off
A multi-gang masonry box or a multi-gang switch box with a
raised cover is recommended for easy installation, although
standard outlet boxes will work. No derating is necessary. See
the Wallbox Requirements tables that follow for the size and
number of outlet boxes required for multi-gang installations.
Fins Broken Off
The fins on the dimmers have special break-off points that allow
removal of partial fin sections for ganging. Use pliers to carefully
bend fin sides back and forth until they break off. These sections
should only be removed at the break-off point to permit proper
ventilation. DO NOT remove side sections on extreme ends of
the gang. See the tables that follow for the size and number of
outlet boxes required for multi-gang installations when all inside
fins are removed.
WALLBOX REQUIREMENTS FOR MONET
INSTALLATIONS (with NO Fins Broken Off)
Wallplate Number of Narrow Wallbox
Cat. No. Fin/Wide Fin Requirements
Controls
MNW10-00 1 Narrow 1-Gang
MNW20-00 2 Narrow 3-Gang
MNW30-00 3 Narrow 5-Gang
MNW40-00 4 Narrow 6-Gang
MNW50-00 5 Narrow 9-Gang
MNW60-00 6 Narrow 10-Gang
MNW01-00 1 Wide 1-Gang
MNW02-00 2 Wide 4-Gang
MNW03-00 3 Wide 7-Gang
MNW04-00 4 Wide 9-Gang
MNW11-00 1 Narrow/1 Wide 4-Gang
MNW21-00 2 Narrow/1 Wide 5-Gang
MNW31-00 3 Narrow/1 Wide 7-Gang
MNW41-00 4 Narrow/1 Wide 8-Gang
MNW51-00 5 Narrow/1 Wide 10-Gang
MNW12-00 1 Narrow/2 Wide 6-Gang
MNW22-00 2 Narrow/2 Wide 8-Gang
MNW32-00 3 Narrow/2 Wide 9-Gang
MNW13-00 1 Narrow/3 Wide 9-Gang
MNW23-00 2 Narrow/3 Wide 10-Gang
MAXIMUM LOAD PER MONET DIMMER
(with Fins Broken Off)
Cat. No. Single 2-Gang > 2-Gang
MNE04 400VA (320W) 300VA (240W) 250VA (200W)
MNF07 7.5A 6A 5.3A
MNF10 10A 8A 7A
MNI06 600W 500W 400W
MNI10 1000W 800W 700W
MNI15 1500W 1250W 1000W
MNM06 600VA (450W) 500VA (375W) 400VA (300W)
MNM10 1000VA (800W) 800VA (640W) 700VA (560W)
MNM15 1500VA (1200W) 1250VA (1000W) 1000VA (800W)
MNX10 1000VA (980W) 800VA (784W) 700VA (686W)
MNX15 1500VA (1470W) 1250VA (1225W) 1000VA (980W)
MNX20-7 2000VA (1960W) 1600VA (1568W) 1400VA (1372W)
MNX30-7 3000VA (2940W) 2500VA (2450W) 2000VA (1960W)
UNDERSTANDING LEVITON CATALOG NUMBERS
First 2 letters – 3rd character – 4th and 5th characters - – 1st suffix 2nd suffix 3rd suffix
Product Name* Type of Load* Rating or Description* character - Voltage character character – Color
MN = Monet I = Incandescent 04 = 400W/VA 1 = 120V L = Lighted W = White
E = Electronic 06 = 600W/VA 7 = 277V 3 = 3-Way I = Ivory
Low Voltage 07 = 7.5 Amp D = Dual Voltage 4 = 4-Way A = Almond
M = Magnetic 10 = 1000W/VA or 10 Amp 0 = NA 0 = NA G = Gray (or GY)
Low Voltage 15 = 1500W/VA B = Brown
X = Mark 10™ 20 = 2000W/VA or 20 Amp E = Black (ebony)
Powerline 30 = 3000W/VA
F = Fan Speed 0R = Remote
S = Switch SA = Small Adapter
7 = Mark 7™ 0–10V (narrow fin)
0 = NA LA = Large Adapter
(wide fin)
* Monet controls use this naming convention in its entirety.
Renoir and Van Gogh lighting controls use only the suffix convention.
Example of 5-gang outlet box with 3 narrow dimmers and
no wide dimmers (note mounting holes)
Fin Removal Procedure
Example of 3-gang outlet box with 3 narrow dimmers and
no wide dimmers (note mounting holes)
WALLBOX REQUIREMENTS FOR MONET
INSTALLATIONS (with Fins Broken Off)
Wallplate Number of Narrow Wallbox
Cat. No. Fin/Wide Fin Requirements
Controls
MNW20-FB 2 Narrow 2-Gang
MNW30-FB 3 Narrow 3-Gang
MNW40-FB 4 Narrow 4-Gang
MNW50-FB 5 Narrow 5-Gang
MNW60-FB 6 Narrow 6-Gang
MNW70-FB 7 Narrow 7-Gang
MNW80-FB 8 Narrow 8-Gang
MNW90-FB 9 Narrow 9-Gang
MNW02-FB 2 Wide 3-Gang
MNW03-FB 3 Wide 5-Gang
MNW04-FB 4 Wide 7-Gang
MNW05-FB 5 Wide 9-Gang
MNW11-FB 1 Narrow/1 Wide 3-Gang
MNW21-FB 2 Narrow/1 Wide 4-Gang
MNW31-FB 3 Narrow/1 Wide 5-Gang
MNW41-FB 4 Narrow/1 Wide 6-Gang
MNW51-FB 5 Narrow/1 Wide 7-Gang
MNW61-FB 6 Narrow/1 Wide 8-Gang
MNW71-FB 7 Narrow/1 Wide 9-Gang
MNW81-FB 8 Narrow/1 Wide 10-Gang
MNW12-FB 1 Narrow/2 Wide 5-Gang
MNW22-FB 2 Narrow/2 Wide 6-Gang
MNW32-FB 3 Narrow/2 Wide 7-Gang
MNW42-FB 4 Narrow/2 Wide 8-Gang
MNW52-FB 5 Narrow/2 Wide 9-Gang
MNW62-FB 6 Narrow/2 Wide 10-Gang
MNW13-FB 1 Narrow/3 Wide 7-Gang
MNW23-FB 2 Narrow/3 Wide 8-Gang
MNW33-FB 3 Narrow/3 Wide 9-Gang
MNW43-FB 4 Narrow/3 Wide 10-Gang
MNW14-FB 1 Narrow/4 Wide 9-Gang
MNW24-FB 2 Narrow/4 Wide 10-Gang
Comentários a estes Manuais