Section 4 – Displaying and Using the Detail Screens
4.4 Profit Optimizer’s DV Detail Display
1/00 Profit Optimizer User's Guide 59
Honeywell Inc.
DV Detail Display – Field Descriptions and User Notes
Field
Description
Field Type Default Access
User Notes
DQP Status
Read-Only No Access
GOOD, CRIT, DROP, or INAC.
See CV, MV, DV, BDV and CC Statuses in Section
2.2 for status descriptions.
WARNING
For bridge DVs, this status should be the same as the
Profit Controller status or the optimizer will not work
properly.
Critical DV
Target ENG
YES/NO targets specify whether the variable
is critical to the controller.
Use This DV
Target ENG
YES/NO targets indicate whether the variable
is used in calculations or dropped.
This target is locked YES when the DV is critical. To
remove this DV from control, set the [CRITICAL DV]
target NO.
Application
Notes
For a descriptive message about a parameter and its CDS location, press the
parameter name (the field, not the target). Press
CLR
to clear the message.