INSTALLATION GUIDE Alarm Control Panel CA10 plus (Program Version 4.7) ® GDAŃSK ca10pi_e 11/03

Página 2 - WARNINGS

8 Installation Guide CA-10 plus SATEL Outputs The CA-10 plus is equipped with 6 programmable outputs: 4 high-current and 2 low-current ones. The O

Página 3

Section 1 - Description of the Control Panel 9 7 - KEYPAD AUX. ALARM - the output starts on triggering the alarm by the user with the ALARM AUX funct

Página 4

10 Installation Guide CA-10 plus SATEL 21 - BYPASS STATUS - the output is active when some zones are bypassed in the system. Operation of the outp

Página 5

Section 1 - Description of the Control Panel 11 39 - NO GUARD CODE – the output is activated by a timer programmed as the partition control TIMER, un

Página 6 - ESTORING

12 Installation Guide CA-10 plus SATEL Three operating modes of the keypad are provided: 1) Text mode. The first line of the display shows the syst

Página 7

Section 1 - Description of the Control Panel 13 Deletion of the code will not cause renumbering of the other users’ access codes. Whenever a new user

Página 8

14 Installation Guide CA-10 plus SATEL arming/disarming the internal partition, while arming/disarming the internal partition only affects the zone

Página 9

Section 1 - Description of the Control Panel 15 the system (e.g. troubles, start of programming mode via a telephone, activation of service mode, etc

Página 10

16 Installation Guide CA-10 plus SATEL Remote Programming – DOWNLOADING In order to facilitate programming, the CA-10 plus panel is equipped with a

Página 11

Section 1 - Description of the Control Panel 17 waiting for a call from the computer for four hours even when the functions of automatically answerin

Página 12

WARNINGS Due to safety reasons, alarm system should be installed by qualified personnel only. Telephone terminals of the panel should be connected t

Página 13

18 Installation Guide CA-10 plus SATEL Figure 1 - Diagrammatic view of control panel main board, version CA10PV

Página 14

Section 2 - Installation of the Control Panel 19 The stabilized voltage of the control panel power supply is 13.6 - 13.8V and is factory set. The „D

Página 15

20 Installation Guide CA-10 plus SATEL IMPORTANT: Do not connect the mains power supply and the battery, until all the remaining connections are co

Página 16

Section 2 - Installation of the Control Panel 21 As the LCD keypad current consumption is larger than that of the LED keypad (particularly with activ

Página 17

22 Installation Guide CA-10 plus SATEL The keypads are not be connected in parallel to one CLK signal (one partition - two keypads), with the excep

Página 18

Section 2 - Installation of the Control Panel 23 GND TAMP C NO +12to detector power supply circuitCOM(detector input)Zn2 X 1,1kΩCOM(power) (input)•

Página 19

24 Installation Guide CA-10 plus SATEL Connection of Signaling Devices COM OUT1 COMOUT2COM OUT3 COM OUT4 COM +KPD+12 VLIMITER2.2ALIMITER2.2ALIMITER

Página 20

Section 2 - Installation of the Control Panel 25 output OUT5output OUT6DB-15fuse WTAT250V/2Ato battery "+"to mainboard AC contactto ground

Página 21 - BEND ASIDE

26 Installation Guide CA-10 plus SATEL Connection of Voice Synthesizer Where the function of alarm messaging with voice announcements is used, a v

Página 22 - Figure 3

Section 2 - Installation of the Control Panel 27 NOTES: • Do not short or touch the serial port RS-232 pins with your fingers. • Prior to connecti

Página 23

CONTENTS GENERAL DESCRIPTION OF THE CONTROL PANEL...5 TECHNICAL DESCRIPTION

Página 24 - Figure 5

28 Installation Guide CA-10 plus SATEL control panel will not start on connecting the battery alone (without the mains power connected), however, i

Página 25 - (power) (input)

Section 2 - Installation of the Control Panel 29 Note: If LCD keypads are installed in the alarm system, call the FS-124 service function in each L

Página 26 - COM OUT1 COM

30 Installation Guide CA-10 plus SATEL Telephone messaging - alarm reporting. The telephone messaging function requires that the following be progr

Página 27

Section 3 - Activation of Selected Functions 31 • alarm system identifier (facility number - one or more for detailed reporting from a big system )

Página 28 - MEFKA printer socket

32 Installation Guide CA-10 plus SATEL the other), the panel cannot report to both stations in the „Station 1 or Station 2” mode and will change th

Página 29

Section 3 - Activation of Selected Functions 33 Modem initialization The program initializes the modem after the „MODEM” item is selected from the „C

Página 30

34 Installation Guide CA-10 plus SATEL • “connection interrupted” – the control panel stopped answering the computer signals. Note: If the control

Página 31

Section 4 - Programming – Service Functions 35 • keypad alarm duration - 60 seconds, • counting times of counters - 30 seconds; counter values - 0,

Página 32

36 LED Keypad of digit pairs (binary). The programming consists in entering a two-digit number and confirming it with the [#] key. The control panel w

Página 33

Section 4 - Programming – Service Functions 37 The × Ø keys scroll the list of the actual hierarchy level. The Ö key permits „entry” to a more detail

Página 34

CONTENTS FS-13 - programming zones displayed in partition 2 keypad (BIT)...43 FS-14 - program

Página 35

38 Service Functions of the LCD Keypad Key Numeric mode Text mode × deletes character before cursor changes character into previous in alphabet Ø

Página 36

Section 4 - Programming – Service Functions 39 Programming of this code in the LED keypad consists in entering three pairs of hexadecimal characters

Página 37

40 Functions Programming Basic Parameters will dial the number until it gets through. Only when the number has been dialed in full, the busy or no an

Página 38 - Service mode

Section 4 - Programming – Service Functions 41 SECOND SET OF OPTIONS (for LED keypad, the LED No. 11 is blinking) No. No. LCD LED Option ON DOWNLOA

Página 39

42 Functions Programming Basic Parameters FS-6 - programming entry delay, exit delay , and alarm time (DEC) The settings refer to the global times an

Página 40

Section 4 - Programming – Service Functions 43 FS-11 - programming partition 4 zones (BIT) The functions FS-8 to FS-11 are used to divide the alarm s

Página 41

44 Functions Programming Assignment must be separately programmed in the keypad itself (see: ¤Installation Guide for LCD Keypad; ¤Keypad Service Func

Página 42

Section 4 - Programming – Service Functions 45 FS-21 - programming partition 2 options (BIT) The function defines which functions are available in th

Página 43

46 Functions Programming Zone Parameters In the LCD keypad, the time is programmed directly in milliseconds from 16 to 4080 (the value is automatical

Página 44

Section 4 - Programming – Service Functions 47 03 - EOL detector (one-parameter - default value) 04 - 2EOL/NC detector (two-parameter – NC detect

Página 45

CONTENTS FS-70 - programming partition 2 event codes (HEX)...58 FS-71 -

Página 46

48 Functions Programming Zone Parameters FS-27 - programming zone options (BIT) Each control panel zone has eight associated options which activate a

Página 47

Section 4 - Programming – Service Functions 49 EXAMPLE: programming the entry delay time (alarm delay) for the following zones: zone 4 - delay

Página 48

50 Functions Programming Output Parameters Functions Programming Output Parameters FS-31 - programming OUT1 output The function makes it possible to

Página 49

Section 4 - Programming – Service Functions 51 30 - TIMER 31 - AUDIBLE ALARM STATUS 32 - FULL ARM STATUS 33 - ARM/DISARM/CLEAR ALARM 34 - KEYPAD A

Página 50

52 Functions Programming Output Parameters EXAMPLE: programming the OUT1 output for the BURGLARY/FIRE ALARM type operation, for 5 minutes, with

Página 51

Section 4 - Programming – Service Functions 53 FS-38 - programming list of zones OUT4 (BIT) The function programs the list of zones associated with t

Página 52

54 Functions programming parameters of transmission to monitoring stations FS-47 - programming monitoring options (BIT) These options define how the

Página 53

Section 4 - Programming – Service Functions 55 • The options 5 and 6 are only meaningful when double-character codes are reported (with 4/2 or 3/2 f

Página 54

56 Functions Programming Identifiers FS-58 - programming partition 4 events identifier for station 2 (HEX) FS-59 - programming system events identifi

Página 55

Section 4 - Programming – Service Functions 57 FS-61 - programming zone tamper alarm codes (HEX) The codes programmed with this function are reported

Página 56

CONTENTS FS-128- zones bypassed on no exit from partition 2 (BIT)...69 FS-129-

Página 57

58 Functions Programming Zone Event Codes No. LCD LED Option ON send ZONE ALARM code 1 OFF do not send ZONE ALARM code ON send ZONE TAMPER ALARM

Página 58

Section 4 - Programming – Service Functions 59 show the programmed code (1 to 4 the first character, 5 to 8 the second character of the code). The LE

Página 59

60 Functions Programming System Event Codes Functions Programming System Event Codes Apart from the events from zones and partitions, the CA-10 plus

Página 60

Section 4 - Programming – Service Functions 61 • The code 4 is recorded in the event log when lack of communication with the station lasted so long

Página 61

62 Functions Programming Dialer FS-88 - programming telephone number 2 (HEX) FS-89 - programming telephone number 3 (HEX) FS-90 - programming telepho

Página 62

Section 4 - Programming – Service Functions 63 FS-96 - programming message 1 (POLPAGER format) FS-97 - programming message 2 (POLPAGER) FS-98 - progr

Página 63

64 Functions Programming Dialer which cannot be reached (when nobody answers the call or the panel receives the busy signal all the time, etc.). The

Página 64

Section 4 - Programming – Service Functions 65 The programming consists in entering four characters from 0 to B (twice two characters), the first cha

Página 65 - 4 5 6

66 Special Functions • MASTER code, partition 3 = 3456 • MASTER code, partition 4 = 4567. FS-111 - programming keypad addresses (BIT) The keypads

Página 66

Section 4 - Programming – Service Functions 67 • start the DLOAD10 program on the computer and select the number of communication port (COM); • ca

Página 67

GENERAL DESCRIPTION OF THE CONTROL PANEL The CA-10 plus alarm control panel is a new version of the hitherto manufactured CA-10. The changes, as com

Página 68 - Partition 1keypad

68 Special Functions messages. If parameters of such signals change, it will be sufficient to specify new data. The programming consists in entering

Página 69

Section 4 - Programming – Service Functions 69 Additional Functions Extra functions, which were added in the process of developing the functional fea

Página 70

70 Additional Functions Option 1 refers to disabling the hardware access to the service mode. If this option is selected, it is only possible to enter

Página 71

Section 4 - Programming – Service Functions 71 Option 1 disables the possibility of arming, if the control panel has detected a battery trouble. When

Página 72

72 Additional Functions which will be sent, occurs in the system, the control panel will start counting the time again. This feature can be disabled b

Página 73

Section 4 - Programming – Service Functions 73 Note: Similarly as in other SATEL control panels, shorting the pins and powering up alone will not

Página 74

74 DLOAD10 After opening the „Modem” window, select the corresponding modem type or click on the „! Change” button to enter data according to the

Página 75 - REMOTE PROGRAMMING – DLOAD10

Section 5 - Remote Programming 75 The modem communication can be started by clicking on the icon (or selecting the „MODEM” command from the „COMM

Página 76

76 Appendix A – Table of HEX Characters Appendix A Table of HEX characters Decimal format (DEC) Binary format (BIN) Hexadecimal format (HEX) State

Página 77

Appendix B - Signaling 77 Appendix B States signaled with LEDs LEDs 1 to 12: • off - zone free (not violated) • on - zone violated • on with a

Página 78 - Table of HEX characters

6 Installation Guide CA-10 plus SATEL TECHNICAL DESCRIPTION OF THE CONTROL PANEL Zones In its basic configuration, the CA-10 plus control panel ha

Página 79 - States signaled with LEDs

78 States signaled States signaled with sound The signals produced to confirm the operation on the keypad: • three short - system arming/disarming

Página 80 - States signaled with sound

Appendix C - Technical Data 79 Appendix C TECHNICAL DATA Control panel supply voltage... AC 230(+10%; -15%

Página 81 - TECHNICAL DATA

80 Appendix C - Technical Data Table 1. Example of panel power supply load estimation and battery selection. No. Loads Max current Mean current

Página 82

CA-10 plus Alarm System - Connection Diagram (detailed description of main board terminals - see p. 17-18). +12 CLK DATA Z1 COM Z2Partition 1 ke

Página 83 - CA-10 plus Alarm

History of the Manual Updates The updates below refer to the manual for the control panel with program version 4.0. Date Program version Descripti

Página 84 - Description of updates

Section 1 - Description of the Control Panel 7 keypad and will send a “zone alarm” code. It is intended for connecting detectors not related to the b