AMX AXD-CP4/PB Especificações Página 233

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 232
Applications Ver. 0002 AP - 29
AP.4 VARIABLE MONITORING
The continuous monitoring of internal variables of the Drive module may be carried out in two
ways: By electrical signals through the digital and analog outputs or by showing their values on
the display of the Programming Module.
For example, to monitor the power of the asynchronous motors (TV50) and the motor torque
on the synchronous ones (TV2) through the analog outputs and to see if the motor is stopped
(SV5) through a digital output:
OP1=TV50 Power variable through channel 1, pins 10/11 of X7.
OP3=10000 Ten Kilowatts per volt
OP2=TV2 Torque variable through channel 2, pins 8/9 of X7
OP4=1000 A thousand deciNm per 10 volts (10 Nm / volt)
OP10=SV5 Closed contact between pins 6/7 of X6 is the motor is stopped.
AP.4.1 PROGRAMMING MODULE AS MONITOR
Internal Drive variables may be monitored permanently on the screen of the Programming
Module.
Select the digital or analog variable from the VARIABLES menu.
Bear in mind that their units are the ones appearing in the Appendix A and when the cursor is
located under the value of a variable, the monitoring is temporarily frozen.
The bottom line shows the name of the
variable. Its full name can be displayed by
pressing the O key. Example:
Vista de página 232
1 2 ... 228 229 230 231 232 233 234 235 236 237 238 ... 363 364

Comentários a estes Manuais

Sem comentários